- Stock: In Stock
- Model: DVP08XN11R
- Weight: 2.00kg
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.
Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
DVP08XN11R Delta PLC 8DO relay output Digital Module Original brand new
Introduction
The DVP series provides different extension units with specific I/O (please refer to Section 1.1 for specifications). The total input and output points can extend to 256 points. If 256 points are exceeded, the ERROR LED of the MPU will flash.
General Specification
Models Items | DVP08XN11 DVP08XP11R | DVP08XM11N DVP16XM01N | DVP-16XN01 | DVP24XP01
| DVP24XN01 DVP32XP01
| DVP24XP00 DVP24XN00 DVP32XP00
|
Power Supply Voltage | 24VDC (-15%~20%) | 100~240VAC (-15%~20%) 50/60Hz +- 5% | ||||
Fuse Capacity | 2A/250VAC | |||||
Power consumption (MAX) | 5W | 5W | 6.5W | 6.5W | 8W | 30VA |
DC24V supply current | -- | -- | -- | -- | -- | 400mA |
Power Protection | -- | DC24V output with short-circuit protection | ||||
Withstand Voltage | 1500VAC(Primary-secondary)1500VAC(Primary-PE)500VAC(Secondary-PE) | |||||
Retentive Power Interruption | Continues operation within 5ms | Continues operation within 10ms | ||||
Insulation Resistance | >5 M at 500VDC (Between all inputs/outputs and earth) | |||||
Noisy Immunity | ESD: 8KV Air Discharge EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV RS: 26MHz~1GHz, 10V/m | |||||
Grounding | The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N (All DVP units should be grounded directly to the ground pole). | |||||
Operation/Storage Environment | Operation: 0~55 (Temperature), 50~95% (Humidity); Storage: -25~70 (Temperature), 5~95% (Humidity) Pollution degree 2 | |||||
Vibration /Shock resistance | Standard IEC1131-2, IEC 68-2-6[1]TEST Fc / IEC1131-2 & IEC 68-2-27 (TEST Ea)
| |||||
Weight (g) | 170/165 | 160/270 | 280 | 434 | 462/442 | 600/580 |