Why buy from us?
We offer competitive prices and quality services!
Ask a Question About This Product
- Stock: In Stock
- Model: DVP08HP11T
- Weight: 1.00kg
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.
Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
DVP08HP11T Delta PLC 4DI 4DO transistor output Digital Module Original brand new
Electrical Specifications
Model Item | 08HM11N 16HM11N 32HM11N | 08HN11R 08HP11T | 08HP11R 16HP11T | 16HP11R 16HP11T | 32HN00R 32HN00T | 32HP00R 32HP00T | 48HP00R 48HP00T |
Power supply voltage | 24VDC (20.4~28.8VDC)(-15%~20%) | 100~240VDC(-15%~10%), 50/60Hz+-5% | |||||
Fuse capacity | 2A/250VAC | ||||||
Power consumption | 1W/1.5W/3.9W | 1.5W | 1.5W | 2W | 30VA | 30VA | 30VA |
DC24V current output | NA | NA | NA | NA | NA | 500mA | 500mA |
Power supply protection | DC24V output short circuit protection | ||||||
Voltage withstand | 1,5000VAC(Primary-secondary), 1,5000VAC(Primary-PE), 500VAC(Secondary-PE) | ||||||
Insulation resistance | >5Mohm at 500VDC (between all I/O points and ground) | ||||||
Noise immunity | ESD: 8KV Air Discharge EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V Digital I/O: 1KV, RS: 26MHz~1GHz, 10V/m | ||||||
Grounding | The diameter of grounding wire shall not be less than that of L,N terminal of the power supply. (When many PLCs are in use at the same time, please make sure every PLC properly grounded.) | ||||||
Operation/storage | Operation: 00C~550C(temperature), 50~95%(humidity), pollution degree 2 Storage: -250C~700C (temperature), 5~95%(humidity) | ||||||
Vibration/shock /immunity | International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) | ||||||
Weight(g) | 124/160/355 | 130/120 | 136/116 | 225/210 | 660/590 | 438/398 | 616/576 |
Digital Input/Output Modules
Model | Power | Input unit | Output unit | ||
Points | Type | Points | Type | ||
DVP08HM11N | 24VDC | 8 | DC Type Sink/Source | 0 | N/A |
DVP16HM11N | 16 | 0 | |||
DVP32HM11N | 32 | 0 | |||
DVP08HN11R | 0 | 8 | Relay: 250VAc/30VDC 2A/1 point | ||
DVP08HP11R | 4 | 4 | |||
DVP16HP11R | 8 | 8 | |||
DVP08HN11T | 0 | 8 | Transistor: 5~30VDC 0.3A/1point at 400C | ||
DVP08HP11T | 4 | 4 | |||
DVP16HP11T | 8 | 8 | |||
DVP32HN00R | 100~240VAC | 0 | 32 | Relay: 250VAC/30VDC 2A/1point | |
DVP32HP00R | 16 | 16 | |||
DVP48HP00R | 24 | 24 | |||
DVP32HN00T | 0 | 32 | Transistor: 5~30VD 0.3A/1 point at 400C | ||
DVP32HP00T | 16 | 16 | |||
DVP48HP00T | 24 | 24 |