We use cookies 🍪
We use cookies and other similar technologies to improve your browsing experience and the functionality of our site. Learn more in our Privacy Policy.

K7M-DR20UE LS PLC New

K7M-DR20UE LS PLC New
K7M-DR20UE LS PLC New
K7M-DR20UE LS PLC New
K7M-DR20UE LS PLC New
K7M-DR20UE LS PLC New
K7M-DR20UE LS(LG) PLC NewLS (LG) PLC K7M-DR20UEProduct Description:Digital input that offers to MAST... Read More
$147.00
Ex Tax: $147.00
  • Stock: In Stock
  • Model: K7M-DR20UE
  • Weight: 0.63kg
1. We typically ship items within three business days after payment is received.
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.

Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
We accept many payments,include Paypal,Bank Transfer etc
Tags: K7M-DR20UE
K7M-DR20UE LS(LG) PLC New

LS (LG) PLC K7M-DR20UE

Product Description:

Digital input that offers to MASTER-K120S series are made to use both of electric current sink and electric current source. To keep use coil load as an output module, maximum opening and shutting frequency is 1 second on and 1 second off.

Features:

Model
Specification(Input)

 Main unit

K7M-DR10UE

K7M-DR14UE

K7M-DR/DRT/DT20U K7M-DR20UE

K7M-DR/DRT/DT30U K7M-DR30UE

K7M-DR/DRT/DT40U K7M-DRT40U

K7M-DR/DRT/DT60U K7M-DRT60U

 Number of input points

 6 points  

 8 points  

 12 points

 18 points

 24 points

 36 points  

 Insulation method

 Photo coupler  

 Rated input voltage

 DC 24V  

 Rated input current

 7mA (Standard Type P0~P3:9mA, Economic Type P0,P1:9mA)  

 Operating voltage range  

 DC20.4 ~ 28.8V (ripple: less than 5%)  

 Max. simultaneous input points

 100% simultaneously On  

 On voltage / On current

 DC19V or higher / 5.7mA or higher  

 Off voltage / Off current

 DC6V or lower / 1.8mA or lower  

 Input impedance

 Approx.3.3kΩ (Standard Type P0~P3:2.7kΩ, Economic Type P0,P1:2.7kΩ)  

 Response time  

Off → On

 0,1,2,5,10,20,50,100,200,500,1000ms (Default : 10ms)  

On → Off

 0,1,2,5,10,20,50,100,200,500,1000ms (Default : 10ms)  

 Common terminal

6 points / COM

 8 points/COM

 12 points/COM

 18 points/ COM

 12points/COM

 18points/COM

 Operating indicator

 LED turns on at ON state of input  

 

Model
Specifications(Output)
 

 Main Unit

 K7M-DR10UE  

 K7M-DR14UE  

 K7M-DR20UE  

 K7M-DR30UE  

 Output point  

 4 points  

 6 points  

 8 points  

 12 points  

 Insulation method  

 Relay insulation  

 Rated load voltage/current  

 DC24V / 2A (r/load), AC220V / 2A (COS Ψ = 1)/1 point , 5A / 1COM  

 Min. load Voltage/current  

 DC5V / 1mA  

 Max. load voltage/current  

 AC250V, DC110V  

 Current leakage when off  

 0.1mA (AC220V, 60Hz)  

 Max. On/off frequency  

 1,200 times/hr  

 Surge Absorber  

 None  

 Life  

 Mechanical  

 More than 20,000,000  

 Electrical  

 Rated on/off voltage/current load 100,000 or more  

 AC200V / 1.5A, AC240V / 1A (COSΨ = 0.7) 100,000 or more  

 AC200V / 1A, AC240V / 0.5A (COSΨ = 0.35) 100,000 or more  

 DC24V / 1A, DC100V / 0.1A (L / R = 7ms) 100,000 or more  

 Response time  

 Off → On  

 10 ms or lower  

?

 On → Off  

 12 ms or lower  

 Operation indication  

 LED is on at on status of output  

 