We use cookies 🍪
We use cookies and other similar technologies to improve your browsing experience and the functionality of our site. Learn more in our Privacy Policy.

H3CA-A AC24-240V/DC12-240V Time Relay NEW

H3CA-A AC24-240V/DC12-240V Time Relay NEW
H3CA-A AC24-240V/DC12-240V Time Relay NEW
H3CA-A AC24-240V/DC12-240V Time Relay NEW
H3CA-A AC24-240V/DC12-240V Time Relay NEW
H3CA-A AC24-240V/DC12-240V Time Relay NEW
H3CA-A AC24-240V/DC12-240V Time Relay NEW
H3CA-A AC24-240V/DC12-240V Time Relay NEW
H3CR-A AC220V OMRON Time Relay NEWOMRON Time Relay H3CR-A AC220VProduct Description:A wide AC/DC pow... Read More
$33.00
Ex Tax: $33.00
  • Stock: In Stock
  • Model: H3CA-A
  • Weight: 0.09kg
1. We typically ship items within three business days after payment is received.
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.

Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
We accept many payments,include Paypal,Bank Transfer etc
Tags: H3CA-A
H3CR-A AC220V OMRON Time Relay NEW

OMRON Time Relay H3CR-A AC220V

Product Description:

A wide AC/DC power supply range greatly reduces the number of timer models kept in stock.

A wide range of applications with multiple operating modes, six modes for 11-pin models and four modes for 8-pin models.

Ecological design with reduced current consumption.

Easy sequence checking with instantaneous outputs for a zero set value.

Length of 80 mm or less when panel-mounted with a P3GA-11 Socket (H3CR-A8E, 100 to 240 VAC, 100 to 125 VDC)

PNP input models available.

Standards: UL, CSA, NK, LR, EN 61812-1, and CE Marking.

Specifications:

General

Item

H3CR-A/-AS

H3CR-AP

H3CR-A8/-A8S

H3CR-A8E

Operating mode

A: ON-delay

A: ON-delay (power supply start)

B: Flicker OFF start

B2: Flicker ON start (power supply start)

B2: Flicker ON start

E: Interval (power supply start)

C: Signal ON/OFF-delay

J: One-shot (power supply start)

D: Signal OFF-delay

 

E: Interval

 

G: Signal ON/OFF-delay (Only for H3CR-A-300)

 

J: One-shot (Only for H3CR-A-300)

 

Pin type

11-pin

8-pin

Input type

No-voltage input

Voltage input

---

Time-limit

H3CR-A/-A8/-AP: Relay output (DPDT)

Relay output (SPDT)

output type

H3CR-AS/-A8S: Transistor output (NPN/PNP universal)*

Instantaneous

---

Relay output (SPDT)

output type

Mounting method

DIN track mounting, surface mounting, and flush mounting

Approved standards

UL508, CSA C22.2 No.14, NK, Lloyds

Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.

Output category according to EN60947-5-1 for Timers with Contact Outputs.

Output category according to EN60947-5-2 for Timers with Transistor Outputs.

*The internal circuits are optically isolated from the output. This enables universal application as NPN or PNP transistor.

Standard (0.05-s to 300-h) Models

Time unit

s (sec)

min (min)

h (hrs)

×10 h (10 hrs)

Full scale setting

1.2

0.05 to 1.2

0.12 to 1.2

1.2 to 12

3

0.3 to 3

3 to 30

12

1.2 to 12

12 to 120

30

3 to 30

30 to 300

Double (0.1-s to 600-h) Models

Time unit

s (sec)

min (min)

h (hrs)

×10 h (10 hrs)

Full scale setting

2.4

0.1 to 2.4

0.24 to 2.4

2.4 to 24

6

0.6 to 6

6 to 60

24

2.4 to 24

24 to 240

60

6 to 60

60 to 600

 

Ratings

Rated supply voltage

100 to 240 VAC (50/60 Hz)/100 to 125 VDC,

(See notes 1 and 2.)

24 to 48 VAC (50/60 Hz)/12 to 48 VDC

 

(24 to 48 VAC/VDC for H3CR-A8E)

 

(See note3.)

Operating voltage range

85% to 110% of rated supply voltage (90% to 110% at 12 VDC)

Power reset

Minimum power-opening time: 0.1 s

Input

No-voltage Input

ON impedance: 1 kΩ max.

ON residual voltage: 1 V max.

OFF impedance: 100 kΩ min.

 

Voltage Input

Max. permissible capacitance between inputs lines (terminals 6 and 7): 1,200 pF

Load connectable in parallel with inputs (terminals 6 and 7).

100 to 240 VAC/100 to 125 VDC

High (logic) level: 85 to 264 VAC/85 to 137.5 VDC

Low (logic) level: 0 to 10 VAC/0 to 10 VDC

24 to 48 VAC/12 to 48 VDC

High (logic) level: 20.4 to 52.8 VAC/10.8 to 52.8 VDC

Low (logic) level: 0 to 2.4 VAC/0 to 1.2 VDC

Power consumption

H3CR-A/-A8

100 to 240 VAC/100 to 125 VDC

(When at 240 VAC, 60 Hz)

Relay ON: approx. 2.0 VA (1.6 W)

Relay OFF: approx. 1.3 VA (1.1 W)

24 to 48 VAC/12 to 48 VDC

(When at 24 VDC)

Relay ON: approx. 0.8 W

Relay OFF: approx. 0.2 W

 

H3CR-AP (See note 3)

100 to 240 VAC/100 to 125 VDC

(When at 240 VAC, 60 Hz)

Relay ON: approx. 2.5 VA (2.2 W) (See note 4.)

Relay OFF: approx. 1.8 VA (1.7 W) (See note 4.)

24 to 48 VAC/12 to 48 VDC

(When at 24 VDC)

Relay ON: approx. 0.9 W (See note 4.)

Relay OFF: approx. 0.3 W (See note 4.)

 

H3CR-A8E

100 to 240 VAC/100 to 125 VDC

(When at 240 VAC, 60 Hz)

Relay ON/OFF: approx. 2 VA (0.9 W)

24 to 48 VAC/VDC

(When at 24 VDC)

Relay ON/OFF: approx. 0.9 W

 

H3CR-AS/-A8S

24 to 48 VAC/12 to 48 VDC

(When at 24 VDC)

Output ON: 0.3 W Output OFF: 0.2 W

Control outputs

Time limit contacts: 5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cosΦ = 1)

Transistor output: Open collector (NPN/PNP), 100 mA max. at 30 VDC max.,

residual voltage: 2 V max.

Instantaneous contact: 5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cosΦ = 1)

Note:

1.DC ripple rate: 20% max. (A single-phase, full-wave-rectification power supply can be used).

2.Do not use an inverter output as the power supply.

3.Models with 24-to-48-VAC or 12-to-48-VDC power supply have inrush current. Caution is thus required when turning ON and OFF power to the Timer with a non-contact output from a device such as a sensor. (Models with an inrush current of approximately 50 mA and a 24-VDC power supply are available (the H3CR-A-302 and H3CR-A8-302).)

4.The values are for when the terminals 2 and 7 and terminals 10 and 6 are short-circuited, and include the consumption current of the input circuit.

Characteristics

 

Accuracy of

±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s or 3 s)

operating time

Setting error

±5% FS ±50 ms *1

Reset time

Min. power-opening time: 0.1 s max.

Min. pulse width: 0.05 s (H3CR-A/-AS)

Reset voltage

10% max. of rated supply voltage

Influence of voltage

±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s or 3 s)

Influence of

±1% FS max. (±1%±10 ms max. in a range of 1.2 s or 3 s)

temperature

Insulation resistance

100 MΩ min. (at 500 VDC)

Dielectric strength

2,000 VAC (1,000 VAC for H3CR-A[]S), 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)

2,000 VAC (1,000 VAC for H3CR-A[]S), 50/60 Hz for 1 min (between control output terminals and operating circuit)

2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)

1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)

2,000 VAC, 50/60 Hz for 1 min (between input and control output terminals and operation circuit) for H3CR-AP

Impulse withstand

3 kV (between power terminals) for 100 to 240 VAC/100 to 125 VDC, 1 kV for 24 to 48 VAC/12 to 48 VDC

voltage

4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC/100 to 125 VDC, 1.5 kV for 24 to 48 VAC/12 to 48 VDC and 24 to 48 VAC/VDC

Noise immunity

±1.5 kV (between power terminals) and ±600 V (between no-voltage input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)

Static immunity

Malfunction: 8 kV

Destruction: 15 kV

Vibration resistance

Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each

Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each

Shock resistance

Destruction: 1,000 m/s2 3 times each in 6 directions

Malfunction: 100 m/s2 3 times each in 6 directions

Ambient temperature

Operating: -10°C to 55°C (with no icing)

Storage: -25°C to 65°C (with no icing)

Ambient humidity

Operating: 35% to 85%

Life expectancy

Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h)

Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) *2

EMC

(EMI): EN61812-1

Emission Enclosure: EN55011 Group 1 class A

Emission AC Mains: EN55011 Group 1 class A

(EMS): EN61812-1

Immunity ESD: IEC61000-4-2: 6 kV contact discharge (level 3), 8 kV air discharge (level 3)

Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)

Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900±5 MHz) (level 3)

Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3)

Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3), 2 kV I/O signal-line (level 4)

Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3), 2 kV line to ground (level 3)

Case color

Light gray (Munsell 5Y7/1)

Degree of protection

IP40 (panel surface)

Weight

Approx. 90 g

*1.The value is ±5% FS +100 ms to −0 ms max. when the C, D, or G mode signal of the H3CR-AP is OFF.

*2.Refer to Data Sheet.

*3.Relay output only.

 