Why buy from us?
We offer competitive prices and quality services!
Ask a Question About This Product
- Stock: In Stock
- Model: H3Y-2
- Weight: 0.05kg
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.
Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
Product Description?
Semi-multi power supply voltage.
Large transparent time setting knob facilitates time setting. A flat-blade and Phillips screwdriver can also be used for time setting.
Pin configuration compatible with MY Power Relay.
LED indication for power and output statuses.
Conforms to EMC standards.
Conforms to EN61812-1 and approved by UL and CSA.
Specifications:
Time Ranges
Rated time | Time setting range | Rated time | Time setting range |
0.5 s | 0.04 to 0.5 s | 3 min | 0.1 to 3 min |
1 s | 0.1 to 1 s | 5 min | 0.2 to 5 min |
5 s | 0.2 to 5 s | 10 min | 0.5 to 10 min |
10 s | 0.5 to 10 s | 30 min | 1 to 30 min |
30 s | 1.0 to 30 s | 60 min | 2 to 60 min |
60 s | 2.0 to 60 s | 3 h | 0.1 to 3 h |
120 s | 5.0 to 120 s | --- | --- |
Ratings
Item | H3Y-2(-0)/H3Y-4(-0) |
Rated supply voltage | 24, 100 to 120 (50/60 Hz), 200 to 230 VAC (50/60 Hz) (See note 1.), |
Operating voltage range | All rated voltages except 12 VDC: 85% to 110% of rated supply voltage |
Reset voltage | 10% min. of rated supply voltage (See note 5.) |
Power consumption | 100 to 120 VAC: |
Control outputs | H3Y-2(-0): 5 A at 250 VAC, resistive load (cosΦ = 1) |
Note:
1.Do not use the output from an inverter as the power supply.
2.With DC ratings, single-phase full-wave rectified power sources may be used.
3.Only the H3Y-2 and H3Y-2-0 Series include 2-VDC models.
4.Use the Timer within 90% to 110% of the rated supply voltage (95% to 110% for 12 VDC) when using it continuously under an ambient operating temperature of 50°C.
5.Set the reset voltage as follows to ensure proper resetting.
100 to 120 VAC:10 VAC max.
200 to 230 VAC:20 VAC max.
100 to 110 VDC:10 VDC max.
Characteristics
Accuracy of operating time | ±1% FS max. (0.5 s range: ±1%±10 ms max.) |
Setting error | ±10%±50 ms FS max. |
Reset time | Min. power-opening time: 0.1 s max. (including halfway reset) |
Reset voltage | 10% max. of rated supply voltage |
Influence of voltage | ±2% FS max. |
Influence of temperature | ±2% FS max. |
Insulation resistance | 100 MΩ min. (at 500 VDC) |
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying metal parts) |
Vibration resistance | Destruction: 10 to 55 Hz, 0.75-mm single amplitude |
Shock resistance | Destruction: 1,000 m/s2 (approx. 100G) |
Ambient temperature | Operating: -10°C to 50°C (with no icing) |
Ambient humidity | Operating: 35% to 85% |
Life expectancy | Mechanical:10,000,000 operations min. (under no load at 1,800 operations/h) |
Impulse withstand voltage | Between power terminals: |
Noise immunity | ±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise) |
Static immunity | Destruction: 8 kV |
Enclosure rating | IP40 |
Weight | Approx. 50 g |
EMC | (EMI) EN61812-1 |
Approved standards | UL508, CSA C22.2 No. 14, Lloyds |
Note:
1.Add ±10 ms to the above value for the 0.5 s range model.
2.Terminal screw sections are excluded.
Caution: In the interest of product improvement, specifications are subject to change without notice.