We use cookies 🍪
We use cookies and other similar technologies to improve your browsing experience and the functionality of our site. Learn more in our Privacy Policy.

H3CR-G8EL AC200-240 Time Relay NEW

H3CR-G8EL AC200-240 Time Relay NEW
H3CR-G8EL AC200-240 Time Relay NEW
H3CR-G8EL AC200-240 Time Relay NEW
H3CR-G8EL AC200-240 Time Relay NEW
H3CR-G8EL AC200-240 Time Relay NEW
H3CR-G8EL AC200-240 OMRON Time Relay NEWOMRON Time Relay H3CR-G8EL AC200-240           Product Descr... Read More
$97.00
Ex Tax: $97.00
  • Stock: In Stock
  • Model: AC200-240
  • Weight: 0.13kg
1. We typically ship items within three business days after payment is received.
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.

Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
We accept many payments,include Paypal,Bank Transfer etc
Tags: AC200-240
H3CR-G8EL AC200-240 OMRON Time Relay NEW

OMRON Time Relay H3CR-G8EL AC200-240           

Product Description:

A wide star-time range (up to 120 seconds) and star-delta transfer time range (up to 0.5 seconds).

Specifications:

Accuracy of operating time

±0.2% FS max.

Setting error

±5% FS ±50 ms max.

Accuracy of Star-delta transfer time

±25% FS + 5 ms max.

Reset voltage

10% max. of rated voltage

Influence of voltage

±0.2% FS max.

Influence of temperature

±1% FS max.

Insulation resistance

100 MΩ min. (at 500 VDC)

Dielectric strength

2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)

2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)

2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)

1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)

Impulse withstand

3 kV (between power terminals)

voltage

4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)

Noise immunity

±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)

Static immunity

Malfunction: 8 kV

Destruction: 15 kV

Vibration resistance

Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions

Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions

Shock resistance

Destruction: 980 m/s2 three times each in six directions

Malfunction: 294 m/s2 three times each in six directions

Ambient temperature

Operating: -10°C to 55°C (with no icing)

Storage: -25°C to 65°C (with no icing)

Ambient humidity

Operating: 35% to 85%

Life expectancy

Mechanical: 20 million operations min. (under no load at 1,800 operations/h)

Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)

EMC

(EMI) EN61812-1

Emission Enclosure: EN55011 Group 1 class A

Emission AC Mains: EN55011 Group 1 class A

(EMS) EN61812-1

Immunity ESD: IEC61000-4-2: 6 kV contact discharge (level 3)

8 kV air discharge (level 3)

Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)

Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900±5 MHz) (level 3)

Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3)

Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3)

2 kV I/O signal-line (level 4)

Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3)

2 kV line to ground (level 3)

Case color

Light Gray (Munsell 5Y7/1)

Degree of protection

IP40 (panel surface)

Weight

H3CR-G8L: approx. 110 g; H3CR-G8EL: approx. 130 g

 

 

Be the first to write a review for this product.

Write a review

Note: HTML is not translated!
Bad           Good