We use cookies 🍪
We use cookies and other similar technologies to improve your browsing experience and the functionality of our site. Learn more in our Privacy Policy.

XBC-DR20SU LS PLC XGB AC100~220V power supply DC 24V input 12 point relay output 8 point 1Year Warranty

XBC-DR20SU LS PLC XGB AC100~220V power supply DC 24V input 12 point relay output 8 point 1Year Warranty
XBC-DR20SU LS PLC XGB AC100~220V power supply DC 24V input 12 point relay output 8 point 1Year Warranty
XBC-DR20SU LS PLC XGB AC100~220V power supply DC 24V input 12 point relay output 8 point 1Year Warranty
XBC-DR20SU LS PLC XGB AC100~220V power supply DC 24V input 12 point relay output 8 point 1Year Warranty
XBC-DR20SU LS PLC XGB AC100~220V power supply DC 24V input 12 point relay output 8 point 1Year Warranty
XBC-DR20SU LS PLC XGB Series Standard Type 12-point DC Input 8-point Relay Output AC100~240V NewPLCA... Read More
$143.00
Ex Tax: $143.00
  • Stock: In Stock
  • Model: XBC-DR20SU
  • Weight: 0.47kg
1. We typically ship items within three business days after payment is received.
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.

Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
We accept many payments,include Paypal,Bank Transfer etc
Tags: XBC-DR20SU
XBC-DR20SU LS PLC XGB Series Standard Type 12-point DC Input 8-point Relay Output AC100~240V New

PLCAGE: XBC-DR20SU LS(LG) PLC XGB Series Standard Type 12-point DC Input 8-point Relay Output AC100~240V New

Features:

XBC/XEC: Terminal block type

*Supporting floating-point arithmetic

*Built-in Cnet, HSC, PID, Positioning, Pulse catch, Input filter, External Interrupt

*Expansion Cnet, Ethernet

*Download port: Serial, USB

XBC/XEC

*Economic type

- CPU processing speed: 240ns/step

- Max 38 I/O points

- Program capacity: 4Ksteps

*Standard type

- CPU processing speed: 94ns/step

- Max. 284 I/O points

- Program capacity: 15Ksteps/200KB(XBC/XEC)

*High performance type

- CPU processing speed: 83ns/step

- Max. 384 I/O points

- Program capacity: 15Ksteps/200KB(XBC/XEC)

Specifications:

Items 

Specifications (“S” type) 

Remark 

XBC-DN20S 

XBC-DR20S 

XBC-DN30S 

XBC-DR30S

Program control method

Reiterative operation, fixed cycle operation, constant scan

 

I/O control method

Scan synchronous batch processing method (Refresh method),

Directed by program instruction

Program language

Ladder Diagram, Instruction List

Number of

instructions

Basic

28

Application

687

Processing speed

(Basic instruction)

94 ns/Step

Program capacity

15 k steps

Max. I/O points

244 point (Main + Expansion 7 stages)

254 point (Main + Expansion 7 stages)

Data area

P

P0000 ~ P1023F (16,384 point)

M

M0000 ~ M1023F (16,384 point)

K

K0000 ~ K4095F (65,536 point)

L

L0000 ~ L2047F (32,768 point)

F

F0000 ~ F1023F (16,384 point)

T

100ms, 10ms, 1ms : T0000 ~ T1023 (1,024 point)

(Adjustable by parameter setting)

C

C0000 ~ C1023 (1,024)

S

S00.00 ~ S127.99

D

D0000 ~ D10239 (10,240 word)

Word

U

U00.00 ~ U0A.31 (Analog data refresh area: 352 word)

Z

Z000~Z127 (128 Word)

R

R0000~R10239 (10,240 word)

Total program

128

 

Initial task

1

Cyclic task

Max. 8

I/O task

Max. 8

Internal device task

Max. 8

Operation mode

RUN, STOP, DEBUG

Self-diagnosis function

Detects errors of scan time, memory, I/O

Program port

RS-232C 1 channel

Back-up method

Latch area setting in basic parameter

Internal consumption current

240 mA

255 mA

Weight(g)

470

475

        