Why buy from us?
We offer competitive prices and quality services!
Ask a Question About This Product
- Stock: In Stock
- Model: N310-4060-H3X
- Weight: 33.00kg
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.
Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
Product Specifications
Single / Three phase, 200-240V model
N310-xxxx-XXX | 20P5 | 2001 | 2002 | 2003 |
Horsepower(HP) | 0.5 | 1 | 2 | 3 |
Max Applicable Motor Output (KW) | 0.4 | 0.75 | 1.5 | 2.2 |
Rated Output Current(A) | 3.1 | 4.5 | 7.5 | 10.5 |
Rated Capacity(KVA) | 1.2 | 1.7 | 2.9 | 4.0 |
Max. Input Voltage | Single/Three Phase: 200~240V +10% -15%, 50/60HZ,+- 5% | |||
Max. Output Voltage | Three Phase: 200~240V | |||
Input Current(A) | 8.5/4.5 | 12/6.5 | 16/11 | 23.9/12.5 |
Net Weight (KG) | 1.4 | 1.4 | 2.5 | 4.0 |
Allowable momentary power loss time (second) | 1.0 | 1.0 | 2.0 | 2.0 |
Three phase, 380 – 480V model
N310-xxxx-XXX | 4001 | 4002 | 4003 | 4005 | 4008 | 4010 | 4015 |
Horsepower(HP) | 1 | 2 | 3 | 5 | 7.5 | 10 | 15 |
Max Applicable Motor Output (KW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 |
Rated Output Current(A) | 2.3 | 3.8 | 5.2 | 8.8 | 13.0 | 17.5 | 25 |
Rated Capacity(KVA) | 1.7 | 2.9 | 4.0 | 6.7 | 9.9 | 13.3 | 19.1 |
Max. Input Voltage | Three phase 380~480V +10%-15% 50/60HZ+-5% | ||||||
Max. Output Voltage | Three Phase 380V~480V | ||||||
Input Current(A) | 4.2 | 5.6 | 7.3 | 11.6 | 17 | 23 | 31 |
Net Weight (KG) | 2.4 | 2.5 | 3.8 | 4.0 | 4.0 | 7.0 | 7.0 |
Allowable momentary power loss time (second) | 1.0 | 1.0 | 2.0 | 2.0 | 2.0 | 2.0 | 2.0 |
General Specifications
Item | N310 TYPE | ||
Control Mode | V/F or Current Vector Control | ||
Frequency Control | Range | 0.01~400.00 Hz | |
Start control torque | 150%/1Hz ( Vector) | ||
Speed control range | 1:100 ( Vector) | ||
Speed Control Precision | +-0.5% (Vector) | ||
Setting resolution | Digital: 0.01Hz, Analog: 0.06Hz/ 60Hz(10bits) | ||
Keypad setting | Set directly with”up””down” keys or the VR on the keypad | ||
Display Function | Five digital LED and status indicator; display frequency/ line speed/ DC voltage/ Output voltage/ Current/ Rotation direction/ Inverter parameter/ Fault Log/ Program Version / Heat sink temperature/PID feed back | ||
External signal setting | 1. External potentiometer0-10V/ 0-20mA 2. Provides up/down controls, speed control or automatic procedure control with multifunctional contacts on the terminal block (TM2) | ||
Frequency Limit Function | Upper/lower frequency limits and three programmable skip frequencies | ||
Carrier frequency | 1~ 15 kHz | ||
V/F pattern | 18 fixed patterns, 1programable curve | ||
Acc/Dec control | Two-stage Acc/Dec time (0.1 – 3,600 seconds) and four-stage S curves (refer to descriptions on 10-07..) | ||
Multifunction analog output | 5 functions (refer to description on 2-12) | ||
Multifunction input | 23 functions (refer to description on 01-00~01-05) | ||
Multifunction output | 14functions (refer to description on 01-09~01-10) | ||
Other Functions | Momentary Power Loss Restart, Speed Search, Overload Detection, 16 preset speeds. Acc/Dec Switch (2 Stages), S Curves, 3-wire Control, PID control, torque boost, Slip Compensation, Frequency Upper/ Lower Limit, Auto energy saving, Modbus slave and PC/PDA Link, Auto Restart, Encoder input. | ||
Communication Control | 1. Control by RS232 or RS485 2. One to one or one to many (RS485 ONLY) control. 3. BAUD RATE/STOP BIT/PARITY/bit can be set | ||
Braking Torque | About 20%, the model below 20HP with built-in braking transistor and the specified external braking resistors can provide 100% | ||
Operation temperature | 14-1200F(-10 ~ 500C) | ||
Storage temperature | 4-1400F(-20 ~ 600C) | ||
Humidity | 0 -95% Relative Humidity(Non-condense) | ||
Vibration | 1G (9.8m/ S2 ) | ||
Enclosure | IP20 | ||
Protective Functions | Overload protection | The relays to protect the motor (the curve can be set) and the inverter (150 % / 1min) | |
Over Voltage | 200V class: DC Voltage>410V 400Vclass: DC Voltage>820V | ||
Under Voltage | 200V class: DC Voltage<190V 400Vclass: DC Voltage<380V | ||
Momentary Power Loss Restart | Restart can be initiated with spin start after momentary power loss in Max 2 sec | ||
Stall Prevention | Stall prevention for Acceleration/ Deceleration/ Operation. | ||
Short-circuit output terminal | Electronic Circuit Protection | ||
Grounding Fault | Electronic Circuit Protection | ||
Other Function | Protection for overheating of heat sink, over torque detection, error contact control, reverse prohibit, prohibit for direct start after power up and error recovery, parameter lock up. | ||