We use cookies 🍪
We use cookies and other similar technologies to improve your browsing experience and the functionality of our site. Learn more in our Privacy Policy.

XGF-HO8A LS(LG) PLC XGT Series 8 Channels DC5/24V High Speed Counter Brand NEW

XGF-HO8A LS(LG) PLC XGT Series 8 Channels DC5/24V High Speed Counter Brand NEW
XGF-HO8A LS(LG) PLC XGT Series 8 Channels DC5/24V High Speed Counter Brand NEW
XGF-HO8A LS(LG) PLC XGT Series 8 Channels DC5/24V High Speed Counter Brand NEW
XGF-HO8A LS(LG) PLC XGT Series 8 Channels DC5/24V High Speed Counter Brand NEW
XGF-HO8A LS(LG) PLC XGT Series 8 Channels DC5/24V High Speed Counter Brand NEW
XGF-HO8A LS(LG) PLC XGT Series 8 Channels DC5/24V High Speed Counter Brand NEWFeatures1. 3 kinds of ... Read More
$1,187.00
Ex Tax: $1,187.00
  • Stock: In Stock
  • Model: XGF-HO8A
  • Weight: 2.00kg
1. We typically ship items within three business days after payment is received.
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.

Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
We accept many payments,include Paypal,Bank Transfer etc
Tags: XGF-HO8A

XGF-HO8A LS(LG) PLC XGT Series 8 Channels DC5/24V High Speed Counter Brand NEW


Features

1. 3 kinds of pulse inputs are available.

(a) If 1-phase is input

(1) Increasing/Decreasing function by means of the applicable program (1-multiplier, 2-multiplier)

(2) Increasing/Decreasing function by means of the B-phase input (1-multiplier, 2-multiplier)

(b) if 2-phase is input, 1-multiplier, 2-multiplier, 4-multiplier increasing/decreasing function by means of the difference in phase.

(c) if CW/CCW is input, increasing/decreasing function by means of A-phase or B-phase.  

2) Preset/Gate function by means of the applicable program.  

3)  6 additional functions are available such as Count Clear, Count Latch, Sampling Count, Input frequency Measure, Revolution Measure per unit time and Count Disable.

4) 7 kinds of compared signals can be outputted at output contact of the built-in transistor through compared based value (Min compared value, Max compared value) and current count value.  

Performance Specifications   

Items

Specifications

Number of channel

8

Count Input signal

Signal

A-phase, B-phase

Input type

Voltage input(Open Collector)

Signal level

DC 5/24V

Counter

Max count speed 

200kpps

Max count speed 

Disable, 100kpps, 10kpps, 1kpps, 0.1kpps

Count range

-2,147,483,648~2,147,483,647

Count type

program setting)

Linear count(if 32-bit range exceeded, carry/borrow occurs)

Ring count (repeated count within setting range)

Input mode

(program setting)

1-phase input

2-phase input

CW/CCW input

Up/Down Setting

1-phase input

Increasing/decreasing operation setting by B-phase input

Increasing/decreasing operation setting by program

2-phase input

Automatic setting by difference in phase

CW/CCW

A-phase input: increasing operation

B-phase input: decreasing operation

Multiplier

function

1-phase input

1/2 multiplier (program setting)

2-phase input

1/2/4 multiplier (program setting)

CW/CCW

1-multiplier

External

output

Output points

1-point/channel: terminal output available

Type

Select single-compared(>,>=,=,<= ,<) or section compared output (included or

excluded)(program setting)

Output type

Open collector output(Sink)

Function to display operation status

Input sign

A-phase, B-phase

Output sign

Out

Operation status

Module ready

Count enable

To be set through program (count available only in enable status)

Preset function

To be set through program

Additional Functions

(program setting)

Count clear, Count latch,

Sampling count (time setting value: 1~60000ms)

Measurement of input frequency

Measurement of counts per hour(time setting value: 1~60000ms)

Count prohibited function(setting by internal input during count operation)

Terminal

80-pin connector

Internal consumed current

600mA

Parts Names