Why buy from us?
We offer competitive prices and quality services!
Ask a Question About This Product
- Stock: In Stock
- Model: DVP04PT-H2
- Weight: 1.00kg
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.
Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
DVP04PT-H2 Delta PLC 4 point 0.1 degree resolution Analog Module Original brand new
Introduction
DVP04PT-H2 is able to receive 4 points of resistance temperature detectors (PT100, PT1000, NI100, and NI1000) and convert them into 16-bit digital signals. Besides, through the user of FROM/TO instructions in DVP-EH2 MPU program, the data in DVP04PT-H2 can be read or written. There are 49 16-bit control registers (CR) in it. DVP04PT-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.1°F).
Electrical Specifications
Power supply voltage | 24 VDC (20.4 to 28.8 VDC) (-15 to +20%) |
Analog output channel | 4 channels/module |
Applicable sensors | 3-WIRE PT100 / NI100 / PT1000 / NI1000 3850 PPM/°C (DIN 43760 JIS C1604-1989) |
Current excitation | 1.53 mA/200 uA |
Range of input temp | See the table in “Temperature/Digital Value Curve” section. |
Range of digital conversion | See the table in “Temperature/Digital Value Curve” section |
Resolution | 16-bit (0.1°C/0.1°F) |
Output impedance | 0.5? or less |
Overall accuracy | +-0.6% when in full scale within the range of 0 to 55°C, 32 to 131°F |
Response time | 400 ms × number of channels |
Isolation | Isolation between digital circuits and analog circuits. 500 VDC between digital circuits and ground 500 VDC between analog circuits and ground 500 VDC between analog circuits and digital circuits 500 VDC between 24 VDC and ground |
Format of digital data | 15 significant bits out of 16 bits are available; in 2’s complement |
Average function | Provided; available for setup in CR#2 to CR#5; Range: K1 to K100 |
Self-diagnosis | Upper and lower bound detection/channel |
Communication mode (RS-485) | ASCII/RTU mode. Communication speed: 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps. ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1). RS-485 cannot be used when connected to PLC MPU. |
Serial connection with DVP-PLC MPU | The modules are numbered from “0 to 7” automatically by their distance from MPU. 0 is the closest to MPU and 7 is the furthest. Maximum 8 modules are allowed to connect to the PLC and will not occupy any digital I/O points. |
Max. rated power consumption | 24 VDC (20.4 to 28.8 VDC) (-15 to +20%), 2.5 W supplied by external power. |
Operation/storage | 1. Operation: 0 to 55°C (temperature), 50 to 95% (humidity), pollution degree 2 2. Storage: -25 to 70°C (temperature), 5 to 95% (humidity) |
Vibration/shock immunity | Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) |
Product Profile & Dimension