Why buy from us?
We offer competitive prices and quality services!
Ask a Question About This Product
- Stock: In Stock
- Model: 6ES7135-0HF01-0XB0
- Weight: 0.55kg
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.
Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
SIEMENS ELECTRONIC MODULE FOR ET 200B 6ES7135-0HF01-0XB0
Product Description:
SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 4AO 0(4)...20MA; +/- 10V, 11 BIT, 12 MBIT/S.
Features:
Supply voltage | |
Rated value (DC) | 24 V; Value at t < 0.5 s: 35 V |
permissible range, lower limit (DC) | 18.5 V |
permissible range, upper limit (DC) | 30.2 V |
Input current | |
from supply voltage L+, max. | 200 mA; Logic |
Power losses | |
Power loss, typ. | 2.4 W |
Hardware configuration | |
Rack | |
Required terminal block | TB8 |
Digital outputs | |
Load resistance range | |
Load impedance in rated range of output , capacitive load, max. | 1 µF |
Analog outputs | |
Number of analog outputs | 4 |
Voltage output, short-circuit protection | Yes; Electronic; max. 1 output in parallel |
Voltage output, short-circuit current, max. | 25 mA |
Current output, no-load voltage, max. | 18 V |
Output ranges, voltage | |
0 to 10 V | Yes |
-10 to +10 V | Yes |
Output ranges, current | |
0 to 20 mA | Yes |
4 to 20 mA | Yes |
Connection of actuators | |
for voltage output 2-conductor connection | Yes |
for voltage output 4-conductor connection | Yes |
for current output 2-conductor connection | Yes |
Load impedance (in rated range of output) | |
with current outputs, max. | 300 Ω |
with current outputs, inductive load, max. | 1 mH |
Cable length | |
Cable length, shielded, max. | 100 m |
Analog value creation | |
Integrations and conversion time/ resolution per channel | |
Resolution with overrange (bit including sign), max. | 11 bit; Two's complement |
Conversion time (per channel) | 1 ms |
Settling time | |
for resistive load | 0.1 ms |
for capacitive load | 3.3 ms |
for inductive load | 0.5 ms |
Errors/accuracies | |
Output ripple (based on output area, bandwidth 0 to 50 kHz) | +/- 0.05 % |
Linearity error (relative to output area) | +/- 0.05 % |
Temperature error (relative to output area) | +/- 0.02 % |
Crosstalk between the outputs, min. | 40 dB |
Repeat accuracy in settled status at 25 °C (relative to output area) | +/- 0.05 % |
Operational limit in overall temperature range | |
Voltage, relative to output area | +/- 0.05 % |
Current, relative to output area | +/- 1 % |
Basic error limit (operational limit at 25 °C) | |
Voltage, relative to output area | +/- 0.2 % |
Current, relative to output area | +/- 0.3 % |
Interfaces | |
PROFIBUS DP | |
Transmission rate, max. | 12 Mbit/s |
Communication functions | |
Bus protocol/transmission protocol | PROFIBUS DP |
Interrupts/diagnostics/status information | |
Alarms | |
Diagnostic alarm | Yes; Parameterizable |
Diagnostics indication LED | |
Bus fault BF (red) | Yes |
Run mode RUN (green) | Yes |
Galvanic isolation | |
between electronic block and PROFIBUS DP | Yes |
Galvanic isolation analog outputs | |
Galvanic isolation analog outputs | No |
Ambient conditions | |
Operating temperature | |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure | |
permissible range, min. | 795 hPa |
permissible range, max. | 1080 hPa |
Relative humidity | |
Operation, min. | 15 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations | |
Operation, checked according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock test | |
checked according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Degree and class of protection | |
IP20 | Yes |
Connection method | |
Inputs/outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
Dimensions | |
Width | 160 mm; EB and TB |
Height | 130 mm; EB and TB |
Depth | 60 mm; EB and TB |
Weight | |
Weight, approx. | 550 g; EB and TB |